Integration
OPC UA, MQTT and REST on one RIMX platform — without replacing the historian
RIMX is built to connect PLC, DCS, SCADA and IIoT through OPC UA, Modbus, MQTT and REST, then store one history for trends, Excel, Python and workflows. That sentence is easy to put on a homepage and easy to implement badly. The last two years of industrial-architecture writing — Unified Namespace primers, Sparkplug practice, OPC Foundation security notes — agree on a split that plants still blur: live hierarchy versus history with status.
What each protocol is for
- OPC UA (IEC 62541) — browsable information model, certificates, SignAndEncrypt across zones. Default for a DCS or SCADA server. Historical Access (OPC 10000-11, 1.05.04, October 2024) if you need a backfill. See our DCS connection note.
- MQTT (often Sparkplug B at the edge) — publish/subscribe, outbound connections that IT firewalls can live with, many package units. Sparkplug fixes topic and payload at the controls edge; enterprise UNS writers (HiveMQ and others) still tell you to flatten or map before IT systems subscribe, and to keep a historian as a subscriber.
- REST / APIs — IT apps, Excel-class tools, and pushing KPI snapshots. Not a substitute for 1-second process collection.
- Modbus — still what skids speak. Wrap it at the edge; do not make it your plant bus.
A sequence that does not explode tag count
- Connect the DCS read-only over OPC UA (certificates, no Write).
- Bring package units and IIoT on MQTT; map topics into the same RIMX naming as the DCS typicals.
- Subscribe RIMX to what you will actually historize. A UNS can carry more live points than you should archive.
- Expose REST for reports and Python for KPIs, soft sensors and residuals.
- If you need a site-wide live hierarchy, add the broker — but do not delay the historian until the UNS programme finishes. Plant-architecture primers are blunt: one line and one report does not need a UNS.
Optional industrial vision (Modbus TCP, RTSP, ONVIF) belongs here too: OK/NG results are worthless if they never sit next to the process tags that explain them. That is an integration problem, not a camera problem.
Questions engineers ask
Is MQTT better than OPC UA for a DCS?
Usually no. OPC UA is the structured, securable path out of a modern DCS. MQTT is the efficient path for many edge nodes and outbound DMZ links. Use both.
Do we need a Unified Namespace project first?
Only if many consumers need the same live hierarchy. One unit and a reporting need is often a historian plus OPC UA. A UNS is current state; RIMX still stores history.
Can RIMX be the MQTT consumer and the OPC UA client?
That is the intended shape: DCS over OPC UA, package units and cameras over MQTT or REST, one historian for Python and dashboards.
Sources
- OPC Foundation, OPC 10000-11 Historical Access 1.05.04 (2024-10-15); OPC UA security recommendations.
- HiveMQ, “Architecting a Unified Namespace for IIoT” — historian as UNS subscriber, Sparkplug vs enterprise topic limits.
- NAMUR / ATP WG 2.1, OPC UA in process automation systems (2024-12-03).